Free Call Australia : 1 800 834 991

Related Products

Omicron UHF 620 Bandwidth Converter

OMICRON UHF 620 Bandwidth Converter 
  • Flexible adjustable measurement bandwidth 
  • Less interference due to narrowband measurements
  • Simple configuration due to broadband measurements

Product Details

OMICRON UHF 620 Bandwidth Converter

The UHF 620 extends the measurable bandwidth of the MPD 600 up to the VHF and UHF frequency range.

Partial discharge can be measured in an additional measurement range of 100 MHz to 2,000 MHz with different frequency bandwidths:

> Narrowband measurements up to 1.5 MHz
> Mediumband measurements at 70 MHz
> Broadband measurements at 1.9 GHz

The UHF 620 is ideal for measuring power transformers and gas-insulated substations (GIS). This unconventional VHF/UHF partial discharge measuring method can be used for commissioning tests as well as for on-site and online diagnostics.

Key features

• Flexible adjustable measurement bandwidth
• Less interference due to narrowband measurements
• Simple configuration due to broadband measurements
• Decoupling of GIS measurement voltage possible
• Controlled directly via MPD software

MEGGER TTR310 Three-Phase Transformer Turns Ratio Test Set Stand-alone or remote-control operation, Accurately measures ratio, phase deviation and excitation current, Field upgradeable wi...
PITE TECH KGX5B Transformer Dissolved Gas Monitor Continuous, on-line intelligent dissolved gas and moisture monitor with enhanced oil recirculation. The latest addition of our KG X serie...
OMICRON Bushing Adapters Accessories for partial discharge measurement products These adapters fit the most common measurement connections for bushings used in high voltage systems. Th...
OMICRON MONTRANO Continuous Online Monitoring System MONTRANO continuously monitors the dielectric condition of insulation in bushings and inside power transformers under load. The system...
OMICRON MCC 205/210 Coupling Capacitors Coupling capacitors - Accessories for partial discharge measurement products The coupling capacitor connects the PD measurement device to the hi...